Signal handling

Signal handling

Five blocks that stand between a raw value and a usable one: scaling, clamping, switching cleanly, limiting how fast something changes, and smoothing noise.

These are the blocks that turn "the sensor says 6234" into something a machine can act on.


SCALE — linear conversion

Maps IN from one range onto another.

Pin Type Meaning
IN input, number the raw value
IN_MIN, IN_MAX parameters (0, 100) the range IN arrives in
OUT_MIN, OUT_MAX parameters (0, 100) the range you want
OUT output, number the converted value

What it is for: every analog input, ever. A 4–20 mA sensor arriving as raw counts, a 0–10 V level, a fieldbus word that means something physical.

raw_pressure ──[SCALE 0..4095 → 0..16]── OUT ──> pressure_bar

Two things worth knowing:

  • It does not clamp. IN below IN_MIN gives OUT below OUT_MIN, and that is intentional — a reading under range is information, not something to hide. Follow it with LIMIT when the consumer needs a guaranteed range.
  • Reversing is legal. Put the larger number in OUT_MIN and the smaller in OUT_MAX and the scale inverts, which is how you handle a sensor wired backwards without touching the wiring.

Scale once, near the input

Convert to engineering units immediately and let the rest of the program work in bar, °C and mm. Logic that carries raw counts around is logic nobody can read — including you, in a year.


LIMIT — clamp

Holds IN inside MN…MX.

Pin Type Meaning
IN input, number the value
MN, MX parameters (0, 100) the allowed range
OUT output, number IN, clamped

What it is for: making sure a value that came from somewhere you do not control — a screen, a recipe, a fieldbus master — cannot ask for something impossible.

setpoint_from_hmi ──[LIMIT MN=20 MX=80]── OUT ──> setpoint

Clamping hides the fact that it clamped

A setpoint pinned at 80 looks exactly like a setpoint of 80. If it matters that somebody asked for more, compare the input with the output and flag it — one EQ and you have an "out of range" indication instead of a silent surprise.


HYST — comparator with hysteresis

Q switches on at IN ≥ ON, and off again only at IN ≤ OFF.

Pin Type Meaning
IN input, number the measurement
ON parameter (100) switch-on level
OFF parameter (90) switch-off level
Q output, bool the switched output

The gap between ON and OFF is the hysteresis, and it is why this block exists: a plain comparison at a single threshold chatters when the measurement sits near it, and everything downstream chatters with it.

What it is for: anything where a number switches something physical. Thermostats above all.

temp ──[HYST ON=22 OFF=20]── Q ──> heating

Heating comes on at 22 and off at 20 — a two-degree swing that stops the relay clacking every few seconds.

ON below OFF inverts it, which is how you get a cooling thermostat: ON=20 OFF=22 switches on when the temperature falls to 20.

How wide should the gap be?

Wide enough that normal noise cannot cross it, and no wider — the swing is felt by whatever the machine does. For temperature, a degree or two. For a pressure switch, a few percent. If you are unsure, watch the raw value in the Scope for a minute and make the gap bigger than the wobble you see.


RAMP — rate limiter

OUT follows IN, but changes at most RATE units per second.

Pin Type Meaning
IN input, number the target
RATE parameter, units/s (10) the fastest OUT may change
OUT output, number the rate-limited value

What it is for: stopping a step change from becoming a mechanical shock. An operator typing a new speed, a recipe changing a setpoint, a mode switch — all of them can move a number instantly, and the machine cannot follow instantly.

speed_request ──[RAMP RATE=50]── OUT ──> speed_setpoint

The request may jump from 0 to 500; the setpoint takes ten seconds to get there.

Two ramps fighting is the classic drive problem

If the drive has its own acceleration ramp and the program ramps the setpoint, the two disagree and the axis overshoots or oscillates. Set the drive's ramps to minimum and let one place own the profile. See Motion blocks.


PT1 — first-order filter

OUT approaches IN with time constant T.

Pin Type Meaning
IN input, number the noisy value
T parameter, ms (1000) time constant
OUT output, number the smoothed value

After T milliseconds the output has covered about 63 % of a step; after about 3×T it has effectively arrived. Bigger T means smoother and slower.

What it is for: a measurement that jumps around more than the thing it measures. A flow meter, a load cell on a vibrating frame, a temperature sensor picking up electrical noise.

raw_weight ──[PT1 T=500]── OUT ──> weight

A filter buys smoothness with delay

A filtered value is always behind reality, by roughly T. Filter a measurement that feeds a fast control loop and you have made the loop slower and less stable — filter as little as you can get away with, and never more than the loop's own response time.

For a value that is only displayed, a filter is nearly free and makes a screen far more pleasant to read.


Putting them in order

The usual chain for an analog input, left to right:

raw ──[SCALE]── engineering units ──[PT1]── smooth ──[LIMIT]── safe ──> logic

Scale first so everything downstream is in real units. Filter second, on a value you can reason about. Clamp last, closest to whatever must not receive nonsense.

Then take the decision with HYST rather than a bare comparison, and the whole path from sensor to relay is quiet, readable and hard to get wrong.