Three widgets that show history rather than the present moment: a trend chart, the traces inside it, and the alarm table.

These are the widgets somebody opens when they want to know why, not what — and a screen that can answer that question saves the walk back to the office for a laptop.


trend

Property Type Default Meaning
series list the traces (see below)
timespan_s number 300 how much time is shown, seconds
sample_ms number 1000 how often a point is taken
autoscale yes/no yes fit the vertical axis to the data
min, max number fixed axis when autoscale is off
grid yes/no yes draw gridlines
show_legend yes/no yes name the traces
scroll_mode yes/no yes scroll, rather than wrap around

A chart of how values have behaved. Up to four traces, sampled in the board — so the history exists whether or not anybody is watching.

timespan_s and sample_ms together decide what you can see. Five minutes at one second per point is 300 points, which is about the width of a panel screen — sensible. Five minutes at 10 ms per point is 30 000 points squeezed into a few hundred pixels, and everything short is lost in the squeeze anyway.

Autoscale is right for watching and wrong for comparing. With it on, a flat line fills the chart and looks dramatic; with a fixed min/max, flat looks flat and two screens of the same variable can be compared. Fix the axis for anything somebody will judge by eye.

For anything short, use the Scope

A trend samples periodically. A pulse one cycle long falls between two samples by construction — and the fault you are chasing is usually exactly that. The Scope records every cycle in the board and stops on a trigger. Trend for behaviour over minutes, scope for what happened in one.


trace

Property Type Meaning
tag variable what this line follows
color colour how it is drawn

One line in a trend. Traces are children of the trend widget — you do not place them on the screen yourself.

Give traces colours that survive being printed and photographed. Somebody will screenshot the board and send it to you, and two similar blues become one blue in the process.


alarm_table

Property Type Default Meaning
filter active / unacked / history / all which alarms to show
min_priority info / warning / fault / critical the lowest priority shown
rows number 8 how many fit
show_time yes/no yes when it happened
show_ack_button yes/no yes let the reader acknowledge
sort newest_first / priority newest_first ordering
font font text size

The list of what is wrong, and what was.

filter decides what the table is for, and it is worth having more than one:

  • active — what is wrong now. The screen somebody looks at when something has stopped.
  • unacked — what has not been seen yet, including things that have already cleared. This is the one that catches the intermittent fault nobody was standing there for.
  • history — what happened, in order. The answer to "it did something odd this morning".

sort by priority when the table is short. With eight rows and a busy alarm situation, newest-first can push the critical one off the bottom while a stream of information messages fills the view.

Timestamps are only as good as the clock

An alarm history with no time is a list of things that happened in an unknown order. Make sure the board's clock is set — from the network, from an RTC, or from the browser — before commissioning, not after. Otherwise the first day's history is stamped in 1970.


Where the history lives

Both widgets read data the board collects, in the board, all the time. Nothing depends on a browser being open or an editor being connected.

That is what makes them worth putting on a screen: the equipment remembers, so the person who arrives afterwards can find out what happened without having been there.