Three blocks that anyone controlling equipment ends up needing, and that ctrl32 ships so you do not have to write them: a motor starter, a valve, and a PID controller.

They are bigger than the rest of the library because they contain the parts that are easy to forget — feedback supervision, latched faults, an acknowledge that only works when it is safe, and an integrator that does not wind up.


MOTOR — start/stop with feedback

Pin Type Meaning
START input, bool start command
STOP input, bool stop command — overrides START
FB input, bool feedback: the motor is actually running
ACK input, bool acknowledge a fault
T_FB parameter, ms (3000) how long feedback may take
CMD output, bool the contactor command
FAULT output, bool latched fault

What it does, in order:

  1. START raises CMD — unless STOP is present, which always wins.
  2. From then on, FB must confirm within T_FB ms. If it does not, FAULT latches and CMD drops.
  3. FAULT stays latched until ACK — and ACK only works at standstill, so nobody can acknowledge a fault into a running motor.
start_pb ──START─┐
 stop_pb ──STOP──┤            ├── CMD   ──> contactor
aux_contact ──FB─┤ MOTOR      ├── FAULT ──> motor_fault
 ack_pb  ──ACK───┘ T_FB=3000

Why the feedback matters. Without it, a blown fuse, a tripped overload or a contactor that welded open looks exactly like a running motor: the command is on and the program is content. With it, the program knows within three seconds that what it asked for did not happen — instead of carrying on as though it had.

Wire the feedback to the thing you want to be sure of

An auxiliary contact on the contactor proves the coil pulled in. A current relay proves current is flowing. A speed switch proves the shaft is turning. Each one catches more failures than the one before it, and costs a little more.

STOP is not an emergency stop

STOP is a command in software. Emergency stop is a wired circuit that removes power without asking the program. See Intended use.


VALVE — open/close with end-position check

Pin Type Meaning
OPEN input, bool open command
CLOSE input, bool close command — has priority
FB input, bool end-position feedback
ACK input, bool acknowledge a fault
T_FB parameter, ms (5000) how long the travel may take
CMD output, bool the valve output
FAULT output, bool latched fault

The same shape as MOTOR, with the timing a valve needs: T_FB defaults to five seconds because a valve has to physically travel, and CLOSE wins over OPEN because closed is the safer state for most processes.

recipe_step ──OPEN──┐
   e_stop_ok ──CLOSE─┤            ├── CMD   ──> valve_solenoid
   limit_sw ──FB─────┤ VALVE      ├── FAULT ──> valve_stuck
    ack_pb  ──ACK────┘ T_FB=5000

A latched FAULT here means the valve did not reach its end position in time — jammed, no air, a broken limit switch, or a travel time that is simply longer than T_FB on a cold morning. All four are worth knowing about.

Set T_FB from the real thing, not the catalogue

Watch the actual travel time in the Scope, then give it generous headroom — perhaps double. A T_FB set too tight produces nuisance faults on a cold morning, and nuisance faults teach whoever is using it to acknowledge without looking, which is worse than no fault at all.


PID — controller

Pin Type Meaning
SP input, number setpoint
PV input, number process value (the measurement)
MAN input, number manual output value
AUTO input, bool TRUE = automatic, FALSE = manual
KP parameter (1) proportional gain
TI parameter, seconds (60) integral time — 0 disables I
TD parameter, seconds (0) derivative time — 0 disables D
OUT_MIN, OUT_MAX parameters (0, 100) output range
OUT output, number the control output
LIM output, bool TRUE while the output is saturated

Note the units: TI and TD are in seconds, not milliseconds. Every other block in the library uses ms; controllers are tuned in seconds everywhere in the world, and matching that convention prevents more mistakes than consistency would.

The three things that make it usable

Anti-windup. When the output is pinned at its limit, the integrator stops accumulating. Without this, a controller that spends ten minutes asking for more than the equipment can deliver builds up an enormous integral, and then overshoots wildly when the process finally responds. LIM tells you it is happening.

Bumpless transfer. In manual (AUTO = FALSE), OUT follows MAN and the integrator tracks it. Switch back to automatic and the output stays where it was, then moves from there. No jump, no bang.

Derivative on the measurement, not the error. A setpoint step would otherwise produce an enormous derivative kick. This one takes D from PV, with a TD/8 filter on it, so changing the setpoint moves the output smoothly.

Tuning, briefly

  1. Start with TI = 0, TD = 0 — proportional only. Raise KP until the process responds briskly and just begins to oscillate, then halve it.
  2. Bring in TI: start around the process's response time in seconds and reduce it until the remaining offset disappears without the loop getting sloppy.
  3. Leave TD at 0 unless you have a slow process with real transport delay. Derivative amplifies noise, and on most projects it costs more than it gives.

Watch it, do not guess

Put SP, PV and OUT on one trend and change one parameter at a time. Ten minutes of watching beats an afternoon of theory, and the trend is the record of what you did.

Filter the measurement before the controller, gently

Noise on PV becomes noise on OUT, and with derivative it becomes a lot of noise. A small PT1 helps — but every millisecond of filtering is a millisecond of delay in the loop, so use as little as works.