Variables

Variables

A variable is the only place in the whole system where a value lives. A widget holds no value, only a reference to a variable; the logic reads and writes variables; Modbus, CANopen and the browser all reach the same ones. That is why the screen, the program and the outside world cannot drift apart — there is nothing to drift.

The variable table is at the same time the PLC's process image.

The variable list of the thermostat example — types, units, deadbands and access in one declaration block


VAR and RVAR

Variables live in lists, and a project has at least one.

Object What it is
VAR a named list of global variables. A project starts with one called VAR; add more from Add Object to group things by area — VAR_Heating, VAR_Conveyor.
RVAR the retain list — its variables survive a power-down. At most one per project, added the same way.

The grouping in VAR lists is for you, not for the program: a variable in VAR_Heating is reached by name exactly like any other. Split them when a single list stops being something you can scan.

Retain is membership, not a checkbox

This is the part worth reading twice. A variable is retained because it is in the RVAR list — not because a flag is set on it somewhere.

That single rule prevents the classic mess: retention declared in two places that disagree, and nobody able to say which values actually survive a restart. Open RVAR and you are looking at the complete list of what the board remembers.

Move a variable in, and it is retained. Move it out, and it is not.

What belongs in RVAR

Things that must be known after power comes back:

  • a piece counter, an hour meter
  • a setpoint somebody typed
  • which step a sequence had reached
  • a latched fault that must not clear itself by a power cycle

What does not: measurements, calculated values, anything the program recomputes on its own within a cycle or two.

Never write retained data on every change

Retain storage has a finite number of write cycles. A variable that changes every cycle and is stored on every change wears the memory out within months.

RVAR is for what you need to remember, not for the instantaneous value of a measurement. If you are unsure whether something belongs there, ask what breaks if it comes back as zero — if the answer is "nothing", leave it in VAR.

FRAM makes this painless

On hardware with FRAM, writes take microseconds and the endurance is practically unlimited, so the whole timing problem around power loss disappears. Where retention matters, it is worth choosing hardware that has it.


What every variable has

Property What it is for
name the only thing you refer to it by; in ST it is an identifier
type BOOL, I16, U16, I32, U32, REAL (f32), STRING, TIME
access ro / rw — for the browser and the operator, not for the logic
source where the value comes from (below)
gain / offset conversion to a physical quantity: y = x · gain + offset
unit, decimals how it is displayed
deadband from what change on it counts as a change

A name must not be an ST keyword

Names like NOT, AND, VAR, REAL, TIME or END_IF become something else in the generated program. The editor refuses them at build time and says which one.


Bits of a word

Every bit of an integer variable is addressable on its own, everywhere the variable itself goes:

  • ST: IF status.5 THEN, mask.0 := ready;
  • Ladder / FBD: a contact, a coil or a block's bool pin binds variable + bit — the picker offers the bit field
  • Screens: the switch and led widgets carry bit:

The index must fit the declared width: bits 0–15 on a 16-bit variable, 0–31 on a 32-bit one. A wrong index, a REAL, a TIME or a bool (a bool is a bit) are refused at build time with the variable named. The index is a constant.

A bit write never loses a neighbour

Writing mask.0 from the logic while a browser switch flips mask.7 is safe — bits are written atomically, so neither writer can undo the other's work.


Where the value comes from

Source Meaning
internal board memory only
modbus from a controller, a drive or a meter — unit, function code, address
canopen an object from a node's dictionary (index/subindex), over PDO or SDO
gpio a local board input or output, optionally inverted
periph a chip pin on a local bus (expander, thermometer, LED)

Word order for Modbus `REAL`

A REAL travels over Modbus in two 16-bit registers, and the word order differs from vendor to vendor. It is the most common source of nonsense values. There is a word_order switch for it — when 23.5 °C reads as 3.4·10³⁸, start there.

SDO never in the cycle

CANopen objects read over SDO are slow and do not belong in the cycle — they are for parameterisation at startup. What belongs in the cycle is PDO. See CANopen.


TIME — a duration the operator can set

Delays belong to the operator, not to a rebuild. That is what a TIME variable is for:

- { name: delay, datatype: time, unit: s, decimals: 1, init: 2500 }
  • the table always holds milliseconds — the logic, the buses and Modbus see an ordinary integer
  • the board shows and edits it in the variable's unit (ms, s, min, h). With unit: s the widget reads "2.5 s", the operator types 2.5 and 2500 is stored
  • min/max on the input widget are in the same unit, so the operator is bounded by numbers they can see
  • in ST it is a TIME, so t1(PT := delay) and delay := T#1s500ms need no conversion

That is how a "preheat time" reaches an operator's screen: an input bound to a TIME variable, and the same variable as the timer's PT.

Time comparisons are unsigned

A TIME runs past 2³¹ ms (24.8 days), which is ordinary for something never switched off. Comparisons are unsigned, so IF t1.ET > T#500ms still holds after a month.


Deadband is not cosmetics

An analog input always has noise. Without a deadband the board repaints the display on every flicker of the last bit, and sends that same flicker over the WebSocket to every connected browser.

Set it larger than the noise and smaller than what you care about: for a pressure resolved to 0.01 bar, 0.05 bar is sensible.

This one field does more for how a project feels to use than any other.


Why reading a variable is the most expensive thing in the cycle

The variable table is lock-free: a value is one naturally aligned 32-bit word and a type never changes after registration, so a reader gets either the old value or the new one, never half of each. The hardware guarantees it and no lock is needed.

Before that, every access paid for a lock — about 1.5 µs per take/give pair, which was 20–100× the memory access it guarded. The control program went from 1.32 ms to 0.30 ms. See Performance and limits.

The practical consequence: keep intermediate results in POU local variables, not in global ones. A global variable is an interface — to the screen, to Modbus, to monitoring. Not scratch space.

A type wider than 32 bits does not fit

LREAL, LINT and a string stored inside the value are unsupported precisely because they would break the lock-free read. Strings are indices into a string table.


A snapshot, not an instant

The renderer and online monitoring both read a snapshot: every value in it is fresh in itself, but it is not a consistent instant across all of them. It never was — a writer updates them one at a time.

For display that is right. When you need two values guaranteed to be from the same cycle, compute them in the logic and write the result.


Limit

512 variables. In practice this is the first thing to run out — before blocks, before compilation. The editor refuses a project over the limit at build time, at your desk.